SEL 171 top2 RC Недельный таймер с дополнительными годовыми программами. Анлогичен SEL 170 top2. Разъем для подключения внешней кнопки управления. Дополнительно подключается GPS анетена для автоматической подстройки текущего времени.
Astronomical time switch with weekly program
Time synchronisation via connection of external DCF or GPS antennas, additional posititioning for astronomical program with GPS (GPS not with 24 V device)
Additional power unit required for GPS if only one device is connected to the antenna
1 channel
External input
Connectable sensors (external selector switch, sequence timer, staircase light function)
Connectable switches (ON or OFF permanent switching, astronomical or special program)
84 memory locations
3 special programs with yearly date function per channel
Fixed public holidays or date ranges and public holidays dependent on Easter
Astronomical times with other night interruption / fixed ON switching
permanent ON or OFF switching
Count-down timer
Astronomical time switch function (automatic calculation of sunrise and sunset times for the whole year)
Offset for adjusting of sunrise and sunset times
Position data via coordinates or country/city lists can be programmed
Fixed ON-OFF switching times can be programmed (e.g. night time interruption)
Simulation of switching times (calculated astronomical times and programmed ON/OFF switching times)
Reversible astronomical mode (evenings ON - mornings OFF or evenings OFF - mornings ON) or can be deactivated
DuoFix spring terminals
For 2 conductors each
Wire or strand (with or without wire end sleeve)
Wire diameter: 0.5 - 2.5 mm
Button for releasing plug-in connection
Text-oriented user guidance in display
Preset date and time
fully operable without mains connection
Interface for OBELISK top2 memory card (PC programming)
2. insertable switching program
Copying programs
Storing programs
10 year power reserve (lithium battery)
Zero-cross switching for relay-saving switching and high lamp loads (not with 24 V devices)
Calculated astronomical switching times
Programmable ON-OFF switching times
Switching preselection
Permanent switching ON/OFF
Integrated operating hour counter
Reset option
Service function for monitoring maintenance intervals
Holiday program
Display back light (can be turned off)
PIN coding
Automatic summer/winter time changeover
can be deactivated
Date rule options are already stored for Europe, the USA and other countries
own date rule options or changeover around set dates are available
Operating voltage 230 – 240 V AC
Frequency 50 – 60 Hz
Width 2 modules
Installation type DIN rail
Type of contact Changeover contact
Switching output Potential-free and phase-independent
Opening width < 3 mm (µ)
Program Weekly program, Astronomical program
Program functions ON-OFF
Number of channels 1
External inputs 1
Number of memory locations 84
Power reserve 10 years
Switching capacity at 250 V AC, cos = 1 16 A
Switching capacity at 250 V AC, cos = 0,6 10 A
Incandescent/halogen lamp load 230 V 2600 W
Energy saving lamps 230 V 22 x 7 W, 18 x 11 W, 16 x 15 W, 16 x 20 W, 14 x 23 W
Fluorescent lamp load (conventional) not corrected 2300 VA
Fluorescent lamp load (conventional) series-corrected 2300 VA
Fluorescent lamp load (conventional) parallel-corrected 730 VA 80 µF
Fluorescent lamp load (electronic ballast) 650 W
Switching capacity min. ca. 10 mA
Shortest switching times 1 min
Time accuracy at 25 °C ± 0,5 s/day (quartz) or DCF77/GPS
Time basis Quartz/DCF77/GPS
Stand-by consumption 1,4 W
Memory card supplied –
Test approval VDE
Type of connection DuoFix spring terminals
Keyboards 4 touch buttons
Housing and insulation material High-temperature resistant, self-extinguishing thermoplastic
Type of protection IP 20
Protection class II according to EN 60 730-1
Ambient temperature -30 °C … +55 °C