LUXA 103-360/2 ИК датчик движения. Потолочный монтаж. Для подвесных потолков. Угол обзора 360°. Зона обнаружения: до 7 м, при высоте установки 2,5 м. Подключаемая нагрузка: ламп накаливания, галогенные 1000 Вт (220 В/10 А); люминисцентных ламп нескомпенсированных 1000 ВА, параллельно скомпенсированных - 400 ВА. 2 выхода - 1 для управления освещением и 1 для управления вентиляцией (HKL 10А). Задание времени задержки отключения освещения (1 сек - 20мин ), задание времени задержки отключения вентиляции (10 сек - 60мин ) . IP 40.
Motion detector (PIR)
Automatic lighting control based on presence and brightness
2 channels
2. Relay for HVAC control with adjustable switch-off delay, presence-dependent, potential-free
Ceiling installation for suspended ceilings
Mixed light measurement suitable for the control of fluorescent, incandescent and halogen lamps
Zero-cross switching for relay-saving switching and high lamp loads
Sensor head can be adjusted downwards by 45° in 15° stages thus allowing detection area to be changed to avoid switching the device on unnecessarily
Ceiling cut-out of 65 – 68 mm diameter
Easy installation via two clamping brackets
System consists of power box and sensor with plugged connection cable
Sensor can easily be removed during painting work and replaced afterwards
Large clamping area for quick installation
Single-handed plug-in installation with captive screws
Instant start-up possible via factory preset
No unintentional adjustment due to covered up controls
Adjustable brightness switching value and switch-off delay
Sensitivity can be reduced to limit detection area
Impulse function
Test function
Operating voltage 230 V AC
Frequency 50 – 60 Hz
Stand-by consumption 1,5 W
Light measurement Mixed light measurement
Number of channels 2
Type of contact NO contact
Installation type Ceiling mounting
Setting range brightness 10 – 2000 lx Infinitely adjustable
Switching capacity light
10 A (at 230 V AC, cos = 1), 3 AX (at 230 V AC, cos = 0.3)
Switching capacity presence 5 A (cos f = 1) 250 V AC/24 V DC
Detection angle 360°
Recommended installation height 2 – 3 m
Light switch-off delay 5 s–20 min
Presence switch-off delay 10 s/15 min/30 min/60 min
Incandescent lamp load 1000 W
Fluorescent lamp load (conventional) parallel-corrected 400 VA
Lamps Incandescent/halogen lamps, fluorescent lamps, energy saving lamps, LEDs
Ambient temperature +0 °C … +45 °C
Protection class II
Type of protection Sensor IP 40, power module IP 20